Catalog No. : FBN36TE020RV

Description:  CIRCUIT BREAKER 3P 20A

UPC: 783164395136

Record Plus½ represents the very latest in molded case circuit breaker design. Utilizing design features such as double-break rotary contact structures and advanced ablative materials to enhance interruption, Record Plus½ is capable of interrupting ratings up to 200kA (FB max is 150kA). High kAIC ratings, selective coordination, reduced arc flash energy, and current limitation embody the core design principles of Record Plus½. FB 100 circuit breakers are supplied with factory installed non-user interchangeable thermal-magnetic trip units and ca n be supplie d with o r wit hout l ugs. FB breakers are available in 1-, 2- and 3-pole versions. Record Plus½ product numbers ending in R or R0 do not include lugs. An R1 suffix indicates that the breaker is supplied with line and load lugs, R2 indicates load lugs, and R3 indicates line lugs. RV suffixed product numbers include load lugs and line connections specifically designed for General Electric type AD panels. All frames use common internal accessories (auxiliary switches, UV releases, shunt trips, and bell alarms) UL listed for field installation. UL listed maximum short circuit ratings at 480VAC are 150kA for the 100A frames and 200kA for the 600A frames. Unless noted otherwise, all circuit breakers and accessories are listed in UL file number E11592. "CIRCUIT BREAKER ; 3P 20A"
View More View Less
For more info visit:  https://electrification.us.abb.com/

Descriptors

Category

Record Plus™ Thermal Magnetic Trip

Product Line

Record Plus

GO Schedule

EH

Specifications

Poles

3

Amperage

20 A

System Voltage

240 Vac
480 Vac
600/347 Vac

Frame Type

FB 100

240 Vac Interrupting Rating

150 KAIC

480 Vac Interrupting Rating

65 KAIC

600/347 Vac Interrupting Rating

25 KAIC

Trip Function

LI

Trip Indication Target

No

Suitable for Reverse Feed

Yes

Lugs

FCALK12

Long Time

Fixed

Short Time

No

Instantaneous

Fixed

Ground Fault

No

Zone Selective Interlock

No

Current Metering

No

Communications

No

Protective Relays

No

Special Markings

HACR

Wire Range (Cu/Al)

14-10 AWG

GSA Compliance

No

Classifications

UL File #

E11592