Alternate Catalog No. : HF9-ROLE
Catalog No. : 1SAT146000R1011
Description: HF9-ROLE Electronic Compact Starter 24 VDC
UPC: 4013614515538
Descriptors
Category |
Electronic Starters |
Specifications
Function |
Reversed-on-line starter with electronic overload protection and emergency stop function |
Horsepower Rating UL/CSA |
Nominal Switching Performance Full Load (power factor = 0.4) 3 hp |
Setting Range |
1.5 ... 9.0 A |
Full Load Amps Motor Use |
6.5 A |
Ambient Air Temperature |
Operation -25 ... +70 °C |
RoHS Status |
Following EU Directive 2011/65/EU |
Maximum Operating Voltage UL/CSA |
Main Circuit 500 V AC |
Ampere Rating UL/CSA |
6.5 A |
Connecting Capacity Main Circuit UL/CSA |
Flexible with Ferrule 1x 24 ... 14 AWG |
Connecting Capacity Control Circuit UL/CSA |
Flexible with Ferrule 1x 24 ... 14 AWG |
Tightening Torque UL/CSA |
Control Circuit 5 ... 7 in-lb |
Standards |
IEC/EN 60947-1 |
Utilization |
Motor Protection |
Rated Operational Voltage |
Main Circuit 500 V AC |
Operational Voltage |
Maximum 550 V AC |
Rated Frequency |
Main Circuit 50Hz |
Rated Control Supply Voltage |
24 V DC |
Rated Input Voltage |
Switching Threshold at Signal <0> -3 ... 9.6 V |
Rated Impulse Withstand Voltage |
Main Circuit 6 kV |
Rated Insulation Voltage |
500 V |
Rated Operational Current AC-51 |
9 A |
Rated Operational Current AC-53a |
6.5 A |
Rated Control Supply Current |
0.04 A |
Rated Uninterrupted Current |
9 A |
Input Current |
0.00 A |
Switching Frequency |
≤ 2 Hz |
Rated Operational Power AC-53a |
3 kW |
Overvoltage Category |
III |
Overload Protection |
Electronic overload protection |
Trip Class |
class 10A |
Number of Poles |
3 |
Power Loss |
Maximum 14,6 W |
Number of Protected Poles |
3 |
Mechanical Durability |
10000 cycle |
Electrical Durability |
30000000 cycle |
Delay Time |
Off, Maximum, Switched Off via Control Input Voltage 80 ms |
Mounting on DIN Rail |
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 |
Mounting Position |
Position 1, load side bottom |
Connecting Capacity Control Circuit |
Flexible with Ferrule 1/2x 1 ... 2.5 mm2 |
Connecting Capacity Main Circuit |
Flexible with Ferrule 1x 2 ... 2.5 mm2 |
Recommended Screw Driver |
Control Circuit M3 |
Terminal Type |
Screw Terminals |
Tightening Torque |
Control Circuit 0.5 ... 0.6 N⋅m |
Wire Stripping Length |
Control Circuit 8 mm |
Response Time |
Phase Asymmetry 33% 120 second [unit of time] |
Pollution Degree |
2 |
Phase Loss Sensitive |
Yes |
Degree of Protection |
Housing IP20 |
Short-Circuit Current Rating (SCCR) |
(500 V AC, 30 A Class J or CC) 100 kA |
Classifications
ETIM 5.0 |
EC001037 - Motor starter combination |
ETIM 6.0 |
EC001037 - Motor starter/Motor starter combination |
ETIM 7 |
EC001037 - Motor starter/Motor starter combination |
eClass |
7.0 27370905 |
Dimensions
Product Net Width |
22.5 mm |
Product Net Height |
99 mm |
Product Net Depth / Length |
114.5 mm |
Product Net Weight |
0.289kg |
Package Information
Package Level 1 Units |
1 piece |
Package Level 1 Width |
150 mm |
Package Level 1 Depth / Length |
115 mm |
Package Level 1 Height |
34 mm |
Package Level 1 Gross Weight |
0.389 kg |
Package Level 1 EAN |
4013614515538 |
Safety Information
Safety Integrity Level (SIL) |
3 |
Safety Category |
3 |
Performance Level |
Up to e |
Mean Time to Dangerous Failure |
Motor Protection 447 year |
Mean Time to Failure |
39.3 year |
Probability of Dangerous Failure per Hour |
3 hour |
Diagnostic Coverage |
0.99 |
Diagnostic Coverage Safe |
0.41 |